Váš košík je prázdný...
PROFINET module for Protos II process transmitter The module is a PROFINET communication unit for Protos II 4400. It features two RJ45 Ethernet sockets and can therefore be connected in a ring or star topology. The module is only intended for operation in ordinary (non-hazardous) locations.
The module is a PROFINET communication unit for Protos II 4400. It features two RJ45 Ethernet sockets and can therefore be connected in a ring or star topology. The module is only intended for operation in ordinary (non-hazardous) locations.
Značka: | |
Kategorie: | Měření a regulace / Měření kapalin / Převodníky |
IO specification | V2.34 |
Conformance class | B (CC-B) |
Network load class | 2 |
Vendor ID | 0×61 (= Knick) |
Device ID | 0×0020 |
Min. cycle times | 1 ms |
Identification & maintenance | I&M1–3, 0 |
Serial interface standard | 100BASE-TX (IEEE 802.3, IEC 61158, IEC 61784) |
Number of AIs | 20 |
Number of AOs | 1 |
RoHS conformity | According to EU directive 2011/65/EU |
EMC | EN 61326–1, EN 61326–2–3, NAMUR NE 21 |
Interference immunity | EN 55011 Group 1 Class A |
Lightning protection | to EN 61000–4–5, Installation class 2 |
Ambient temperature | –20 to 55 °C |
Relative humidity | 5 to 95 % |
Climatic class | 3K5 according to EN 60721–3–3 |
Location class | C1 according to EN 60654–1 |
Screw clamp connectors | Single or stranded wires 0.2 to 2.5 mm2 |
Wiring | Stripping length max. 7 m |